For areas with high safety requirements or rough conditions,
compliance with DIN 18032-3 and DIN 57710-13 for indoor stadium.
Car Washing Room | Machine Factory | Food Factory | Warehouse | Indoor Stadium










A variety of suspension
brackets can be clicked
into the trunking groove
Connect trunking sections
Select electrical phase at
the unit
Click lighting unit into
trunking rail
| Beam angle | H |
| DS 25° | <3m |
| 30° | 6-12m |
| 60° | 5-10m |
| 90° (WD) | 3-5m |
| 120° (PMMA) | 2-5m |
| 120° (PC) | 2-4m |






| Model NO. | Watt | lm | lm/W | Function | Length(mm) |
| RIP5P-60-P2 | 58W-50W-42W-32W by switch | 10,000 | 170 | ON/OFF | 1450 |
| RIP5P-75-P2 | 75W-67W-53W-46W by Switch | 12,500 | 168 | ON/OFF | 1450 |
| RIP5P-75-PC | 75W-67W-58W-51W-43W- 37W-28W-22W by Switch | 12,500 | 168 | ON/OFF | 1450 |
| RIP5P-60-P/B4 | Max 60W | 10,000 | 170 | DALI2 (1-100% DIM) | 1450 |
| RIP5P-75-P/B4 | Max 75W | 12,500 | 168 | DALI2 (1-100% DIM) | 1450 |
| RIP5P-70-BB | Max70W by Switch | 11,500 | 170 | 0-10V | 1450 |
| Model NO. | Watt | lm | lm/W | Function | Length(mm) |
| RIP7P-64-P2 | 64W-55W-46W-36W by switch | 11,200 | 175 | ON/OFF | 2025 |
| RIP7P-73-PC | 73W-66W-58W-52W-42W- 35W-27W-22W by switch | 12,800 | 175 | ON/OFF | 2025 |
| RIP7P-88-P2 | 88W-72W-62W-54W by switch | 15,000 | 170 | ON/OFF | 2025 |
| RIP7P-129-P2 | 129W-109W-90W-72W by Switch | 21,500 | 168 | ON/OFF | 2025 |
| RIP7P-60-P4 | Max 60W | 10,500 | 175 | DALI (1-100% DIM) | 2025 |
| RIP7P-90-P4 | Max 88W | 15,000 | 170 | DALI (1-100% DIM) | 2025 |
| RIP7P-129-P4 | Max 129W | 21,500 | 170 | DALI (1-100% DIM) | 2025 |
| Model NO. | Wiring | Description | Length(mm) |
| TKB53-05W-00 | 5x 2.5 mm² | L1, L2, L3, N. E | 1450 |
| TKB53-07W-00 | 7x 2.5 mm² | L1, L2, L3, N, E+, D+, D- | 1450 |
| TKB53-26W-00 | 6×2.5+2×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +2×1.5 mm² D+, D- | 1450 |
| TKB53-66W-00 | 6×2.5+6×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +6×1.5 mm² D+, D-, EL1, EL2, EN1, EN2 | 1450 |
| Model NO. | Wiring | Description | Length(mm) |
| TKB73-05W-00 | 5x 2.5 mm² | L1, L2, L3, N. E | 2025 |
| TKB73-07W-00 | 7x 2.5 mm² | L1, L2, L3, N, E+, D+, D- | 2025 |
| TKB73-26W-00 | 6×2.5+2×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +2×1.5 mm² D+, D- | 2025 |
| TKB73-66W-00 | 6×2.5+6×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +6×1.5 mm² D+, D-, EL1, EL2, EN1, EN2 | 2025 |
| Model NO. | Wiring | Description | Length(mm) |
| TKB93-05W-00 | 5x 2.5 mm² | L1, L2, L3, N. E | 2900 |
| TKB93-07W-00 | 7x 2.5 mm² | L1, L2, L3, N, E+, D+, D- | 2900 |
| TKB93-26W-00 | 6×2.5+2×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +2×1.5 mm² D+, D- | 2900 |
| TKB93-66W-00 | 6×2.5+6×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +6×1.5 mm² D+, D-, EL1, EL2, EN1, EN2 | 2900 |
| Model NO. | Wiring | Description | Length(mm) |
| TKB143-05W-00 | 5x 2.5 mm² | L1, L2, L3, N. E | 4050 |
| TKB143-07W-00 | 7x 2.5 mm² | L1, L2, L3, N, E+, D+, D- | 4050 |
| TKB143-26W-00 | 6×2.5+2×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +2×1.5 mm² D+, D- | 4050 |
| TKB143-66W-00 | 6×2.5+6×1.5 mm² | 6×2.5 mm² L1, L2, L3, N, E, CHR, +6×1.5 mm² D+, D-, EL1, EL2, EN1, EN2 | 4050 |